Crestron Commercial Lighting Design Guide
Doc. 4775B | Crestron.com 63
Accessories
GLS-PLS
The GLS-PLS is a 3-phase power loss sensor designed for use with Crestron
Green Light systems to activate Override mode during a power failure. In
response to a signal from the GLS-PLS, the lighting system program can be
temporarily overridden while designated emergency lighting circuits are changed
to their override preset levels and unnecessary lighting and other devices are shut
down to minimize the demand on emergency power equipment.
The GLS-PLS senses each leg of a 120 or 277 Volt 3-phase feed, providing LED
indication of the status of each phase on its front panel. When power is lost on
any phase, the corresponding status LED turns off and a contact closure is
activated on each of two control outputs. Two isolated control outputs are
provided to allow for interfacing with third-party equipment in addition to the
Crestron lighting system. Each contact closure output is rated for 1A @ 24VDC.
Testing the GLS-PLS-120/277 is facilitated using three Test Switches located
behind a small cover plate on the front of the unit. Setting any switch to the TEST
position simulates a loss of power on the corresponding phase leg, providing a
test of the unit's internal circuitry and any connected equipment.
The steel enclosure is designed for mounting to a vertical surface. Conduit
knockouts are provided on the bottom, top, and both sides. All electrical
connections are made via screw terminals accessed by removing the front panel.
UL924
Underwriters Laboratories specifies safety standards for emergency lighting and
power equipment under UL924. The GLS-PLS power loss sensor will help satisfy
UL-924 requirements.
Control Protocol Interfaces for 3
rd
Party Devices
GLA-BMS
The GLA-BMS is an Ethernet based "protocol translator" which allows a Crestron system to communicate directly
with any number of building management protocols. Programmable like any other Crestron Ethernet device, the
GLA-BMS makes it easy to interface with:
BACnet/IP
BACnet/MSTP (RS-485)
Modbus TCP/IP
Modbus RTU (RS-485)
Lonworks
Metasys N2 Open (Johnson Controls)