Professional Automation Control System Crestron PAC2
8 • Professional Automation Control System: PAC2 Operations Guide – Doc. 5941A
Connectors, Controls & Indicators
# CONNECTORS
1
,
CONTROLS &
INDICATORS
DESCRIPTION
1 NET (and LEDs)
(A – H)
(32) 4-pin 3.5 mm detachable terminal blocks
comprising (4) Cresnet ports (paralleled) per
each of (8) segments
24: Power (24 Vdc)
Y: Data
Z: Data
G: Ground
(8) Yellow LEDs indicate Cresnet
communications on each respective segment
2 LEFT, RIGHT
(2) 5-pin 0.156 inch headers;
Module interconnect ports, connect to
CLX-Series lighting control modules using
included interconnect cables
3 POWER (and LEDs)
(1 - 4)
(4) 3-pin 3.5 mm detachable terminal blocks
comprising (1) Cresnet power selection
connecter per each of (4) power groups;
Connect to external Cresnet power supply or
to internal power supply via jumpers, to
power Cresnet devices connected to the
NET ports;
Maximum load per power group using
external supply: 75 watts (3.125 amps @ 24
Vdc);
Maximum total load using internal supply: 50
watts (2 amps @ 24 Vdc);
(4) Green LEDs indicate 24 Vdc power
present at each respective power group
4 I/O (1 - -8)
(1) 9-pin 3.5 mm detachable terminal block
comprising (8) “Versiports” – digital
input/output or analog input ports;
Digital input: Rated for -024 Vdc; input
impedance 20 kΩ; logic threshold 1.24 Vdc;
Digital output: 250 mA sink from maximum
24 Vdc; catch diodes for use with “real world”
loads;
Analog input: Rated for 0-10 Vdc, protected
to 24 Vdc maximum; input impedance 20 kΩ;
Programmable 5 volts, 2 kΩ pull-up resistor
per pin;
All ports referenced to ground
5 OVERRIDE
(1) 3-pin 3.5 mm detachable terminal block
comprising (2) inputs from external contact
closures to trigger the preset override state in
CLX-Series modules connected to the
module interconnect ports;
Maximum input: 1- mA at 5 volts
(Continued on following page)