Crestron CNX-B2/B4/B6/B8/B12 Single Gang Keypads
Operations & Installation Guide - DOC. 8173A Single Gang Keypads: CNX-B2/B4/B6/B8/B12 7
Industry Compliance
As of the date of manufacture, the keypads have been tested and found to
comply with specifications for CE marking and standards per EMC and
Radiocommunications Compliance Labelling (N11785).
NOTE: This device complies with part 15 of the FCC rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Setup
Network Wiring
CAUTION: Use only Crestron power supplies for Crestron equipment.
Failure to do so could cause equipment damage or void the Crestron
warranty.
NOTE: When installing network wiring, refer to the latest revision of
the wiring diagram(s) appropriate for your specific system configuration,
available from the Downloads | Product Manuals | Software and Wiring
Diagrams section of the Crestron website (www.crestron.com)
.
When calculating the wire gauge for a particular Cresnet run, the length
of the run and the power factor of each network unit to be connected
must be taken into consideration. If Cresnet units are to be daisy-chained
on the run, the power factor of each unit to be daisy-chained must be
added together to determine the power factor of the entire chain. If the
unit is a home-run from a Crestron system power supply network port,
the power factor of that unit is the power factor of the entire run. The
length of the run in feet and the power factor of the run should be used in
the resistance equation on the next page to calculate the value on the right
side of the equation.